Mutual inductance parameter measurement and experimental research of
double circuit based on different frequency method
Abstract
In order to improve the measurement accuracy of mutual inductance
parameters of transmission lines in the en-vironment of double circuit
power lines without power outage, this paper establishes simulation
models for measuring mutual inductance parameters of transmission lines
using the different frequency method in two modes: equal and unequal
zero sequence self-parameters of two circuit lines, using a parallel
zero sequence coupling model of double circuit power lines. In the
article, simulation analysis is conducted on the line parameters with a
coupling coefficient between 0.4 and 0.6 and a line length of
20km-50km.In order to further verify the correctness of the simulation
model and measurement methods, a test bench was established based on the
principle of line mutual inductance parameter testing in a laboratory
dual circuit line without power outage environment for experimental
testing. By comparing the test values under experimental conditions with
the standard values, it has been proven that the model and method can
meet the actual measurement requirements of engineering.