A protection scheme based on dual criterion of active injection and
virtual voltage for distribution network line with T-connected
distributed photovoltaic and load
Abstract
This paper firstly analyses the fault equivalent circuit of DG(
Distributed Generation) as a high-frequency harmonic source, and then
deduces the fault characteristics of the electrical quantities at both
ends on the basis of high-frequency harmonic injection, pointing out the
weaknesses: easily affected by the load capacity of the T-connected
load. Afterwards, this paper draws the equivalent circuit diagram of the
positive sequence component after the fault and derives the difference
expression of the virtual electrical quantity at the opposite end under
internal or external faults at different locations, and then analyses
the fault characteristics of positive sequence under the industrial
frequency. On this basis, this paper proposes a double-terminal
protection scheme based on the combination of high-frequency harmonic
injection and virtual positive sequence differential principle. Finally,
the protection scheme is verified on the MATLAB/SIMULINK platform that
it is not affected by the type of fault, transition resistance, location
of the fault and capacity of T-connected load.